It is important to know how to size smoke vents (also known as AOVs') correctly, in order to install the correct smoke ventilation system in a residential building, otherwise the system will not be compliant.
In residential buildings, the most common approaches to smoke control are natural ventilation and/or mechanical smoke ventilation systems. With natural ventilation, automatic opening vents installed on either the side or roof of the building will open when triggered to allow smoke to escape from the building - they act very much in the same way as opening a regular window would. With mechanical ventilation systems, powered vents actively pull smoke out of the area they are installed to protect in the event of a fire.
There are different approaches to sizing vents for each of these solutions. In this blog, we will cover the guidance from Approved Document B and also provide some advice from Colt Group's designers. We have been an approved installer for Colt smoke control systems for over 40 years, and are Northern Ireland’s sole distributor for Colt smoke control equipment.
You should make sure that the building needs smoke vents by checking against Approved Document B to the building regulations. If the building does not comply with Diagram 3.9 of approved document B, every corridor or lobby next to each stair should have a smoke vent.
The vent needs to be:
For buildings incorporating natural smoke ventilation, the building must comply to one of the following:
The smoke vent should discharge into a vertical smoke shaft, closed at the base, meeting all of the following criteria:
The shaft should conform to the following conditions:
The free area of all the following vents should be a minimum of 1m² in the following places:
The smoke shaft should be constructed from a class A1 material. All vents should either be a fire door set or fitted with a fire and smoke damper. The shaft should be vertical from base to head with a maximum of 4m inclined at no more than 30 degrees.
For a residential smoke control system using natural ventilation, we will typically use a 1000x1700 (millimetres) smoke vent into the smoke shaft to achieve the minimum free area required of 1.5m². Therefore, this requires a smoke shaft that has at least 1m in width as the hole that the vent goes into is 1000x1700mm. For reference there is a render of one below.
All of these vents comply to the relevant standards, and are CE marked in accordance with BS EN 12101-8. We will not install vents that do not meet BS EN 12101-8 into locations that require such a vent.
Mechanical ventilation systems are typically used where natural ventilation is not feasible. This might be because there is no wall in the lobby that connects to the external façade of the building, or because there is not enough space for natural ventilation, such as not having enough space for a full-size smoke shaft. It is normally made up of a natural shaft with extract fans at the top that suck smoke out of the lobbies.
There is not really a minimum size that mechanical vents can be, due to the nature of the system being a replacement where natural is not feasible for whatever reason. However, the smaller they are the quicker smoke travels across them, and it is recommended to not exceed 5m³/s across the vent. Typically, mechanical smoke vents that Colt install are about 800x600mm or larger. But it is project dependent and Colt designers and technical consultants will advise the best size for a mechanical system based on the performance objects and project constraints.
Mechanical smoke ventilation systems should be shown to demonstrate conditions in the lobby or corridor that are equivalent to (or better than) the natural ventilation system it replaces. This is normally done through Computational fluid dynamics analysis.
A mechanical smoke ventilation system using a shaft should be in accordance with:
Each of the above points also apply to natural smoke shafts.
To speak with a member of our team, or book a site survey, contact us today.